22
DISPLAY CODES & MESSAGES (Continued)
Zone 1 relay off,
should be on
Relay found in the wrong state
1) Circuitry failure
2) Relay failure
Zone 2 relay off,
should be on
Zone 3 relay off,
should be on
Zone 1 relay on,
should be off
Zone 2 relay on,
should be off
Zone 3 relay on,
should be off
External relay contact
welded / cut
External relay check input
remained open (0 volts)
while the zone was de-
energized
When the zone is de-energized (RED)
your external relay must close with
1/4 sec.
External relay contact
short
External relay check input
remained closed (voltage
applied) while the zone was
energized
When the zone is energized the
secondary pole of your external relay
(N.C.) must open up within 1/4 sec.
The master and slave
processors disagree on which
sequence they are on
Could have an electrical noise
problem causing one of the
processors to loose sequence
Microprocessor failed the
internal memory test
Watchdog circuitry failure
Electrical noise getting into the
control box causing the
corrupted data.
Place MOV's across the coil of any
device (outside this control) switched
on/off by the relay outputs of this
controller
Serial data
transmission
incomplete
Electrical noise getting into the
control box causing one of the
computers to reset
Master relay on,
Slave relay off
The master processor
disagrees with the slave
Slave relay on,
Master relay off
The slave processor disagrees
with the master